The AMS Monitoring Alarm Systems are ideal for above as well as below ground storage tank monitoring applications the include "High Level" and "Low Level" and Leak Detection. The AMS panel comes standard with auxiliary contacts for interfacing to remote alarms, computer tank gauging systems and auto dialers. Specifications * Primary supply voltage is 120VAC. (plus) + 10%, minus 15% * Output sensor voltage: Nominal 12 VAC @ 6ma. RMS * Temperature Range: -40 degrees F to +150 degrees F. * Contact Rating: 120 VAC or 30 VDC, 5A 1/10 H.P. * Contact life: Electrical @ rated load = 100,000 cycles minimum Mechanical = 10,000,000 cycles * Auxiliary Contacts rated: 120 VAC or 30 VDC 10A 1/3 H.P. * Auxiliary Contacts Design: SPDT (1 form "C") per channel * L.E.D. Indication Lights rated for 100,000 hours * Lights and Pushbuttons rated at NEMA 4X * U.L. 913/508 listed control * U.L. 698-A enclosed controls relating to hazardous locations * One (1) through four (4) Channels Enclosure 10x6x8 * Five (5) through eight (8) Channels Enclosure 14x12x6 Features: * Low Cost * Audible / Visual Alarm * NEMA 4X Fiberglass Enclosure * 100,000 Hour Life L.E.D. Lights * Easily Installed and Wired * Reliable and Flexible * 1-8 Channels Standard * U/L 698-A Relating to Hazardous Locations * Form "C" Auxiliary Contacts Standards
![]() | ![]() | ![]() | ![]() |